HomeFaq Technology Center

2024-03-11

French Standard: NF P92-501 – Class M Fire Test for Building Materials

French Standard: NF P92-501 – Class M Fire Test for Building Materials

The following content will explain the flame retardant and fire test standard NFP92-501 for floor materials:
 

NFP92-501 Fire Safety: Class M Fire Test for Building Materials – Standard Name: 

  •  NF P92-501: Safety against fire: Building materials – Reaction to fire tests. used for rigid material or flexible materials thicker than 5mm

  • NF P92-501: Fire Safety: Construction Materials - Combustion Reaction. Rigid materials and flexible materials with thickness greater than 5mm 

 

NFP92-501 Fire Safety: Class M Fire Testing of Building Materials – Standard Overview: 

NF P 92-501 This regulation contains test methods for the fire performance of building and decorative materials 

 

NFP92-501 Fire Safety: Class M Fire Test for Building Materials - Scope of application of the standard: 

  • Rigid material 

  • Materials for rigid base materials (floors, etc.) 

  • materials with thickness greater than 5mm 

 
NFP92-501 Fire Safety: Class M Fire Test for Building Materials - Standard Analysis: 
NF P 92-503 is divided into levels M0 to M4 for fire protection testing, with M0 being the highest level.

Pay attention to the following points during the test:

  • Burning duration

  • Height of the flame

The sample is inserted into a closed chamber at an angle of 45 degrees to the horizontal and 30 kW/m2 of thermal radiation is exposed to the lowest surface of the sample. Pilot flames are placed above and below the sample to ignite any volatile gases released. After ignition, remove the ignition flame from the sample and the sample flame will extinguish.
1710136423923374                       
                         
 grade judgment (NFP 92-507):
M1 - Non-flammable 0 < q < 2.5
M2 - Low flammability 2.5 < q < 15
M3 - Moderately flammable 15 < q < 50
M4 - Flammable q > 50
 

relevant test standards 

NF P92-510: Determination of upper calorific potential

NF P92-503: Fire safety of building materials-Flexible materials test 

NF P92-504: Fire safety of building materials-Burning rate test 

NF P92-505: Fire safety of building materials - Droplet test

 NF P92-507: Fire safety of building materials-Grade determination 

-------------------------------------------------- ----------------------------------------------